10.25.2010

Roof and Attic Ventilation

Roof Ventilation Update

The construction industry's leading researcher explains why what we think is true often isn't, and how some of our best hunches, based on observation of field performance, have paid off with problem-free attic assemblies

by William B. Rose

I've gotten many calls over the years about attics and attic ventilation; almost invariably the caller is confused, having heard different things from different people. In this article, I'll discuss the performance of attic assemblies and try to shed light on why there are so many points of view about roof ventilation.

Research Findings
The temperature of a northern-climate roof we monitored throughout the 1990s is shown below (Figure 1). Here is a summary of the study: The roof gets cold at night and is hot during the day. It gets hotter on a sunny day than on a cloudy day. Attic assemblies with openings to the outdoors ("vented" attics) stay a bit cooler during the daytime than unvented assemblies. They also stay slightly warmer at night.


Figure 1. Sheathing temperatures are affected somewhat by roof ventilation, but many other factors play a bigger role.

Many factors influence the temperature on the roof. A prioritized list might include hour of day, outdoor air temperature, cloud cover, color of the roof, roof orientation, where the measurement is taken (sheathing or shingles, top or bottom), latitude, wind speed, rain or snow on the roof, heat conduction across attic insulation, roof framing type (truss or cathedral), and attic ventilation to the outdoors. As you can see, ventilation falls pretty far down the list.

To better understand how wind affects roof ventilation, Canadian researchers T.W. Forest and I.S. Walker measured the air exchange rate in attic assemblies using tracer gases. The graph below (Figure 2) gives us a feel for what they found. That is, air-change rates in the attic tended to increase with wind speed, but the amount of air change at a given wind speed was unpredictable. In fact, even with specific information about climate, construction type, and wind speed and direction, the resulting air-change rates may vary by a factor of 10 or more. Whether air flows out through a roof opening or in through that opening, and whether this airflow induces flow from indoors into the attic or helps dilute and remove moist air from the attic, can never be pinned down very well, except to say that wind is a more powerful factor than buoyancy (the "stack effect").


Figure 2. While higher wind speeds tend to increase attic ventilation, the relationship is a weak one: Ventilation rates at a given wind speed can vary by a factor of 10.

For the most part, roof assemblies behave like any wood structure — they are wetter when cold and drier when warm. Roof assemblies tend to be hot, thanks to the sun, so they tend to be dry. Of course, if the roof leaks, that becomes the biggest source of wetness. High moisture levels indoors or in basements or crawlspaces can also increase moisture levels in the roof. Roof members can become particularly wet or covered with frost near holes in the ceiling or leaks in attic ductwork, where humid air enters the attic. It was the formation of local frost "walnuts" like those shown on the next page (Figure 3) that led researchers in the late 1930s to recommend attic ventilation. (If only they had offered to seal up the ceiling instead!)


Figure 3. Moist interior air leaking through a hole in the ceiling can produce moldy sheathing or frost on a roof truss. This photo by the author shows results from the Attic Performance Project.

Many attic assemblies are built with vents to the outdoors on the presumption that outdoor air will enter the attic and dilute moisture coming from indoors or from the foundation. The further presumption is that indoor air is wet and outdoor air is dry. Both of these assumptions are often false. If there are openings in the ceiling, then air movement in the attic can induce airflow from below, or dilute air from below, or do nothing, in ways that are just plain unpredictable no matter how much research is done. Attic air movement can also induce flow into the living space below, which is a nasty problem when the air conditioning is running.

Observations in the Field
Suppose that the picture of attic ventilation provided by physics, described above, doesn't quite cut it. Too many qualifications; nothing pinned down. Then we can go to our own observations and experiences, subjective and incomplete as they may be. Here's my main finding: Attic assemblies built over the last 15 years or so are pretty good. They may be a crapshoot in building-physics terms, but the crapshoot is heavily biased toward good performance.

Let's look at attic assemblies by component:

Truss construction seems to do quite well. There are disasters that occur during construction. Truss uplift continues to be a problem requiring cosmetic fixes. The industry has, for the most part, discontinued the use of fire-retardant treatment of truss members, thereby avoiding what was a serious concern for several years. The truss heels in many cases still fail to provide the height necessary for good insulation. Attics have become a forest of truss webs, and thus are less usable for attic storage space. But the overall picture is good (at least by my observations).

Gypsum wallboard ceilings have shown improvement. The message seems to have gotten out that ceilings must be airtight — there is no justification, summer or winter, for allowing indoor air or foundation air to pass into attic cavities. The common culprits, such as framed soffits over kitchen cabinets, open oversized plumbing or mechanical chases, and leaky can lights, are going away in most construction where the word has gotten out. Weatherization of existing buildings has kept the focus on closing off any ceiling bypasses. In my experience, most truss-framed attics do fine without special vapor-barrier membranes in the ceiling, but in cold locations, cathedral ceilings may need vapor protection just as walls do.

Insulation. Regarding insulation, most areas of the country have healthy amounts in the attic — R-30 in general and R-38 in northern areas. Cellulose provides good insulation and helps block airflow. Fiberglass, in sufficient density and with good installation, also provides good thermal insulation. Foam insulation is being used more commonly, and has become the material of choice for residential air-sealing. Structural insulated panels (SIPs) work fine, as long as the airflow problem at joints is addressed. Foam insulation has been sprayed on the underside of board and wood-panel sheathing with great success. Insulated panels (often polyisocyanurate) make for good roof-deck assemblies, as we know from commercial low-slope construction, where the foam insulation is often sandwiched between the structural roof deck and the roofing membrane. (All foam needs fire protection, of course.) Open-cell foams such as Icynene may need more vapor protection than closed-cell foams, which have greater resistance to vapor flow.

Vapor barriers still cause squabbling, but most builders know that moisture flow from below comes mostly through holes in the ceiling. Cathedral ceilings require special care in insulation placement and vapor protection. But the new code provisions should encourage insulated sheathing materials or insulated "sandwich" assemblies that resist moisture transport and heat flow as a package. With these roof assemblies (I call them "insulated vapor retarders" or "fat vapor retarders"), the inside surface stays close to indoor conditions, the outside surface stays close to outdoor conditions, and nothing bad happens in the middle. Our laboratory has had such an assembly in place for more than 15 years, with one inch of foil-faced polyisocyanurate insulation directly beneath the OSB decking; the sheathing gets hot during the day, but the OSB above the foam insulation is the driest sheathing of all. Remember: Hot means dry.

Ductwork in unconditioned attic assemblies is not ideal. It's best to place all ductwork in conditioned spaces.

OSB has become the universal sheathing material, by economic and environmental necessity. But we still know too little about the moisture performance of this material, such as under what conditions it will begin to fail. In my laboratory, we have seen the material swell by 50 percent or more under extreme conditions. Will it begin to show signs of sagging between trusses, or will workers be putting their feet through it at the time of reroofing? I don't know, but the absence of signs of product failure in the field — at least to my drive-by observations — is reassuring. Nevertheless, I look forward to the day when the marketplace provides a product with more clearly established performance characteristics. I'll be a strong supporter.

Shingles. I'm reviewing the condition of the shingles installed on our research laboratory in 1989; after 18 years, signs of aging are appearing. We hope to conduct laboratory tests to pin down and better quantify the shingle performance and the factors that influence it. The aging we see shows some temperature effect: The white shingles are in better shape than the dark, and a few of the most aged-looking shingles are found on the hottest bay, the one with foam directly on the underside of the sheathing. Without the numbers to go by, we must rely on observation, and our observations suggest that performance depends on other factors besides the presence or absence of ventilation and whether the assembly is truss-framed or cathedral ceiling.

Of course, natural weathering tests that began 18 years ago say little about shingles that are made today. I sense that the shingle industry is currently producing dimension shingles that seem to lie quite flat, resist wind uplift, and hang on to their UV-protecting granules. I don't know how to reroof over dimension shingles, and it does seem unfriendly to the landfill to have that much more mass in the shingle. Nevertheless, my drive-by observations show a lot of good-performing shingles going on roofs over the last couple of decades, and that is very reassuring.

Roof vents. Many years ago, we measured the "net free area" of about a dozen ridge-vent materials. (We used an apparatus that measures the pressure drop across a vent device with great accuracy.) We found that ridge vents with large openings (minimum opening dimension around 1/4 inch) had an equivalent net free area very close to their rated capacity. Vent devices with small openings — or with filter fabrics, or scrims — performed much worse, as much as 75 percent less than their rated area. (If you want to know how restrictive a vent device is, use your imagination — if it looks like air would have a hard time moving through, it probably does.)

This discrepancy would be a big deal, I suppose, for someone who felt that vent regulations were critical to attic performance. I don't, so for me, having vent devices with less airflow than advertised is not a cause for concern.

Building Codes
You — and your building code inspectors — may be unaware that the 2006 version of the IRC for one- and two-family dwellings permits attic construction with no ventilation of the attic cavity. This new provision, R806.4, is largely due to the efforts of Joseph Lstiburek, Armin Rudd, and their colleagues. In brief, unvented conditioned attic assemblies are permitted when an air-impermeable insulation such as rigid foam is applied in direct contact to the underside/interior of the structural roof deck, with sufficient thickness — given the climate — to prevent condensation on the underside (see "Insulating Unvented Attics With Spray Foam," 3/07).

This new provision is a direct challenge to the rule of thumb that has been in place for 50 years, which says that you have to vent a steep-roof attic so the ratio of net free vent area to the projected roof area is 1-to-300 (or 1-to-150 when using "cross ventilation" rather than soffit and ridge vents). This ratio arose from observations of frost on protruding nail points in Wisconsin homes by researchers at the Forest Products Laboratory in 1937, and frost on aluminum plates in research "doghouses" at the University of Minnesota in 1938, under "outdoor" conditions of -13°F.

The Federal Housing Authority turned these findings into the famous 1-300 ratio in 1942, to be applied as a minimum building requirement for the small homes in its financing program. The requirements were picked up by model codes and others following World War II, and the rest, as they say, is history. Shingle manufacturers did not begin piggybacking their warranties on venting regulations until reports of shingle problems began piling up following the change in asphalt sources in the early 1980s.

To Vent or Not
Every designer and builder should be able to produce good attic and roof assemblies, both with and without ventilation — or anything in between — with just part of a conventional ventilation system. For example, from our studies, roof assemblies that have holes but not necessarily straight airflow paths (one gable end vent, or soffit-only) should also be candidates for good performance. And although unvented roof assemblies can perform well, there are still good reasons to vent: The truss-framed, steep-roof attic with an insulated ceiling has been the workhorse of single-family construction, and ventilation works well with this construction, at least in the northern United States.

In some cases, there are also good reasons not to vent: in wildfire areas, in complex cathedral ceiling assemblies, in existing and historic buildings that have never had ventilation, in shed roofs beneath clerestory windows, with foam insulation (foam and ventilation do not go together — think fire), and in complex roof assemblies that combine steep and low-slope construction. I've also heard persuasive arguments against venting in hurricane-prone regions, but I'm not an expert in that area. In short, since critical performance doesn't hinge on ventilation, then either vent, no-vent, or an in-between "kinda"-vent can be taken as the starting point. Whether the choice works or not depends mostly on other factors.

So you should vent where venting is appropriate and not vent where it is not appropriate. As it turns out, the worst-performing, most mold-ridden attics I have seen were vented — with a flooded crawlspace and a direct path for air movement from the crawlspace to the attic. You can mess up a vented attic by allowing such airflow. You can mess up an unvented attic as well, usually by not providing vapor protection appropriate to the climate and indoor moisture levels. Tight ceilings would be a great first step toward moisture control, summer and winter.

Conclusions
The father of a colleague of mine says that when the word "ventilation" comes out, people stop using their heads. Vented assemblies often perform well, but not always. Sometimes roofs appear to be vented but actually aren't. Still, we can take comfort in the observation, based on years of experience, that our attic assemblies are pretty darn good, and — in my opinion — they're getting better. We need to constantly be on the lookout for new conditions and new problems, as they crop up.

Those of you working in the trenches should continue to build in a way that complies with code and that you know works for your climate. For more information about ice damming, summer cooling load, shingle service life, and moisture issues, visit www.fpl.fs.fed.us/documnts/pdf1999/tenwo99a.pdf (TenWolde and Rose, "Issues Related to Venting of Attics and Cathedral Ceilings"). For all four of these concerns, ventilation makes a contribution that is generally more positive than negative, but it hardly ever makes the difference between success and failure.

For the most part, the focus of codes, researchers, designers, and builders on roof ventilation is misplaced. Instead, the focus should be on building an airtight ceiling, which is far more important than roof ventilation in all climates and all seasons. The major causes of moisture problems in attics and roofs are holes in the ceiling and paths for unwanted airflow from basements and crawlspaces. People should focus first on preventing air and moisture from leaking into the attic. Once this is accomplished, roof ventilation becomes pretty much a nonissue.

William B. Rose is a research architect with the Building Research Council at the University of Illinois at Urbana-Champaign, and the author of Water in Buildings: An Architect's Guide to Moisture and Mold. This article was adapted from The JLC Guide to Moisture Control.

--
Scott's Contracting
scottscontracting@gmail.com
http://stlouisrenewableenergy.blogspot.com
http://greenmeupscotty.wordpress.com

Radiation, Convection, Conduction-Warm to Cold

Convection is the movement of air in response to heat

When air is heated, it expands, and therefore becomes less dense, so it rises. The rising warm air displaces cooler air, which sinks. When the motion is constant, it's called a convective loop.

Woodstoves and windows cause convective loops by heating or cooling (respectively) the air closest to them.

Even in homes with airtight walls and ceilings, convective loops can feel like a cool draft and be uncomfortable to the people in the room.

Convective loops can occur inside poorly insulated wall cavities, too, degrading the performance of the insulation.


Heat flows through materials by conduction

Conduction is the flow of heat energy by direct contact, through a single material or through materials that are touching.

Substances that conduct heat readily are called conductors, while substances that don't conduct heat readily are called insulators. Metal is a good conductor; foam is a good insulator. Wood falls somewhere in between.

Radiation heats objects, not air

Radiation is the transfer of heat by electromagnetic waves that travel through a vacuum (like space) or air.

Radiation cannot pass through a solid object like plywood roof sheathing. When the sun shines on asphalt shingles, heat is transferred to the plywood sheathing by conduction. After the plywood has been warmed by conduction, it can radiate heat into the attic.

Radiant barriers are materials (for example, aluminum foil) with a low-emissivity (low-e) surface. Although radiant barriers have a few applications in residential construction—they are sometimes integrated with roof sheathing—they are rarely cost-effective when compared to conventional insulation options.

-- Scott's Contracting scottscontracting@gmail.com http://www.stlouisrenewableenergy.blogspot.com http://www.stlouisrenewableenergy.com scotty@stlouisrenewableenergy.com

Insulating Roofs, Walls, and Floors

ABOUT INSULATING ROOFS, WALLS, AND FLOORS

Its not unusual for a house to have three or four types of insulation: spray foam, loose fill, rigid foam, and/or batts. Each type has multiple uses, but most also have limitations on where they can be used.

The best insulation for each location depends on a number of factors, including cost, ease of installation, available space, and the material's resistance to moisture.
All insulation types perform best when they're installed well. Some (like batts and blankets) can lose significant R-valuewith even a slightly sloppy installation.


Grading installation quality

The Residential Energy Services Network (RESNET), a national association of home-energy raters, long struggled with the question of how to estimate the R-value of walls that vary widely in performance depending on the skill of the insulation installer. Eventually, RESNET developed a useful rating system for insulation installation quality. The system is described in an article published in the January/February 2005 issue of Home Energy magazine, "Insulation Inspections for Home Energy Ratings," by Bruce Harley. The RESNET rating system recognizes three levels of insulation installation quality: Grade I, Grade II, and Grade III.



Grade I is the best installation


"In order to qualify for a Grade I rating, insulation must … fill each cavity side to side and top to bottom, with no substantial gaps or voids around obstructions (that is, blocking or bridging—as seen in the grade II photo below), and it must be split, or fitted tightly, around wiring and other services in the cavity. In general, no exterior sheathing should be visible through gaps in the material," Harley wrote. "Compression or incomplete fill amounting to 2% or less of the surface area of insulation is acceptable for Grade 1, if the compression or missing fill spaces are less than 30% of the intended fill thickness (that is, 70% or more of the intended insulation thickness is present)."

The standard for a Grade II installation is somewhat lower


"A Grade II rating represents moderate to frequent defects: gaps around wiring, electrical outlets, plumbing, other intrusions; rounded edges or 'shoulders,' larger gaps, or more significant compression. No more than 2% of the surface area of insulation missing is acceptable for Grade II."

Grade III installations are the worst
"A Grade III rating applies to any installation that is worse than Grade II." For further information on the RESNET grading system—including illustrations of good jobs and sloppy jobs—see "Assessing the Quality of Insulation Installed in New York Energy Star Labeled Homes."



ABOUT INSULATING FOUNDATIONS

Basements

Because foundations aren't really exposed to vast temperature swings, less insulation is needed there. Insulation in a basement should be chosen to do more than slow the flow of heat through these relatively stable environments; the best choices of basement insulation stop air and water, too. Basement walls and floors can be insulated on the inside or the outside, inside being the easier method for retrofits and outside being easier (in general) for new construction.

Exterior insulation choices should be moisture tolerant


Below-grade walls and floors should be insulated on the outside with, spray foam, or rigid mineral wool. Because polyisocyanurate can absorb water, it should not be used under a slab or on the outside of a foundation. Polyisocyanurate performs well, however, when used on the inside wall of a basement or crawlspace.

The most common insulation under slabs is XPS, although EPS also works if its density is adequate and if it is rated for ground contact. If the insulated slab must bear heavy loads, XPS is usually a better choice than EPS.

Closed-cell spray polyurethane foam can also be used under a slab.
Basement walls can be insulated on the exterior or interior with EPS, XPS, spray polyurethane foam, or rigid mineral wool (for example, Roxul drainboard).

To insulate a basement wall from the inside, the foam should be applied directly to the concrete, in order to keep moist interior air away from the cool, damp surface and lower the risk of condensation. To allow any accumulated moisture to dry to the inside, a semipermeable foam (EPS or XPS) is the best choice. To meet code requirements for a thermal barrier, the foam will probably need to be protected with a layer of gypsum drywall; fiberglass-faced drywall is more moisture resistant than paper-faced drywall.

Under no circumstances should fiberglass batts be used to insulate basement walls. Because fiberglass batts are air-permeable, they are unable to prevent moist interior air from contacting colder basement walls. That's why fiberglass-insulated basement walls can easily become damp and moldy.

Crawlspaces

Although some builders insulate the floor above a crawlspace (the crawlspace ceiling), most building scientists recommend building a sealed, insulated crawlspace that includes wall insulation. It usually requires less insulation (and involves fewer tricky details) to cover a short wall around the perimeter than the whole floor.

Sealed crawlspaces should be built and insulated exactly like basements.
Of course, a well-detailed insulated crawlspace needs more than just insulation. Among the other critical details are careful air-sealing of the rim-joist area and (if the crawlspace has a dirt floor) installation of a ground cover.

Slabs on grade

Some builders insulate slab perimeters without insulating under the slab. In all but the warmest climates, however, it's better to install a continuous layer of EPS, XPS, or spray polyuyrethane foam under the entire slab. Some builders modify an ICF  for use as a form for the slab that includes insulation.

If the home has in-floor radiant heat, it's especially important to include a thick layer of foam directly under the entire slab. Experts disagree on exactly how much foam to add, but they all agree that at least some is a good idea. Engineer John Straube of Building Science Corp. says that after about 4 in.—perhaps 6 in. if the slab includes radiant heat—the money is better spent elsewhere. However, Passivhaus builders sometimes install up to 14 in. of sub-slab insulation.

Soil has a measurable R-value, so it can insulate the bottom of the slab from the exterior air to some extent. But soil is also a nearly infinite heat sink. The average soil temperature varies depending on the climate and the soil depth; however, if the soil has an average temperature of 55°F and the interior of a house has an average temperature of 72°F, heat will always want to flow from the warm side of the slab toward the soil. That's why it's important to insulate under a slab.

ABOUT INSULATING ABOVE-GRADE WALLS

The strategy adopted for insulating a home's above-grade walls depends on the wall construction used.
  • Walls built from SIPs or ICFs already include insulation.
  • Concrete-block  walls are best insulated from the exterior with rigid foam or spray polyurethane foam.
  • Wood-framed walls can be insulated with cavity insulation (fiberglass batts, sprayed-in-place fiberglass, cellulose, or spray polyurethane foam), on the interior (with rigid foam board), on the exterior (with rigid foam board or spray polyurethane foam), or with a combination of approaches (for example, some cavity insulation and exterior foam sheathing).
Thermal bridging
The effective R-value of a framed wall assembly with cavity insulation is always less than the R-value of the insulation alone, as thermal bridging through the studs degrades the performance of the wall. Thermal bridging can be reduced, and the thickness of the wall increased, by:
  • adding foam sheathing to the exterior of the wall;
  • adding a layer of rigid foam under the interior drywall; or
  • building a double-stud wall with staggered studs.
Foam sheathing


The performance of any wood-framed wall will be improved by installing exterior rigid foam sheathing; the usual choices are XPS or polyisocyanurate. Although EPS can be used, it is more fragile than the other two options.
Adding foam insulation to the outside of a wall affects the wall's ability to dry out when it gets wet. Different types of foam insulation have different permeance ratings, but after a few inches they're all pretty impermeable to moisture. Most foam-sheathed walls are designed to dry to the inside. This means that interior plastic vapor barriers should never be used on foam-sheathed walls.

According to Joseph Lstiburek and Peter Baker of Building Science Corp. (see link below), adding 1 in. of R-5 insulation to a 2x6 wall insulated with fiberglass batts increases the effective R-value of the wall from 14.4 to 19.4, a 35% gain with only a 15% increase in wall thickness.

Adding 2 in. of foam raises the R-value from 14.4 to 23.8, an improvement of 65%. A layer of insulating foam on the outside of walls also reduces the risk of condensation by raising the dew point of the surface where water vapor is likely to collect.

Thick foam sheathing is safer than thin foam sheathing. To learn more about determining a safe thickness for exterior foam, see "Calculating the Minimum Thickness of Rigid Foam Sheathing."

ABOUT INSULATING FLAT CEILINGS

Flat ceilings under unconditioned attics can be insulated with fiberglass batts, blown fiberglass, or blown cellulose, but cellulose works best—especially in very cold temperatures when convective loops can degrade the performance of fiberglass. Regardless of the type of insulation used, more is always better, and it's usually an inexpensive upgrade as space is less of a limiting factor than it would be for walls.

Spray polyurethane foam can also be used to insulate a flat ceiling, although at a much higher cost than cellulose. An advantage of spray foam is that it air-seals as it insulates. With all types of attic insulation, air-sealing before insulating is almost more important than type and depth of insulation.

Attic-floor insulation should extend over the top plates of perimeter walls. To provide enough room for the necessary depth of attic insulation, be sure to specify raised-heel roof trusses.

Locating insulation at the attic floor has several advantages over locating insulation along the slope of the roof:
  • It's cheaper, easier, and faster to install thick insulation at the attic floor.
  • Unconditioned attics are easier to vent than insulated rafter bays.
  • It's easier to detect and pinpoint roof leaks when the attic is unconditioned.

ABOUT INSULATING ROOFS

Sloped ceilings and roofs can be insulated from above (by installing rigid foam on top of the roof sheathing), by installing insulation between the rafters, from below (by installing rigid foam under the rafters), or by a combination of some or all three of these insulation methods. Any of these methods will work. Although installing insulation on top of the roof sheathing is more foolproof, it's also less common.
EPS
,or polyisocyanurate foam can be installed above roof sheathing. Two or more layers of rigid foam with staggered seams can be topped with eave-to-ridge 2x4s to create vent channels, followed by a second layer of roof sheathing. Exterior insulation like this with staggered seams disrupts conductive heat flow through the framing assembly.

Installing insulation in rafter bays is risky, as interior moisture can migrate through the insulation (either by diffusion or by piggybacking with exfiltrating air) and contact the cold roof sheathing, leading to condensation. This problem can be prevented by using closed-cell spray polyurethane foam, with or without a ventilation channel under the roof sheathing.

ABOUT RETROFITTING INSULATION

Although adding insulation to an existing home is always more challenging than insulating a new home, weatherization contractors have developed many cost-effective methods of improving existing insulation levels.

It's important to manage any moisture problems in a home before engaging in air-tightening measures or insulation improvements. Inspect the home to identify any leaks or high-moisture areas, and be sure that the home is equipped with adequate mechanical ventilation.

Among the tried-and-true methods used by experienced weatherization workers:
  • To insulate a basement floor, install a continuous layer of XPS foam on top of the concrete. Top the foam with 2x4 sleepers and a plywood subfloor. If a low ceiling makes every inch critical, the sleepers can be omitted; in that case the plywood subfloor should be mechanically fastened through the foam to the concrete.
  • Basement or crawlspace walls can be insulated with interior XPS, EPS, or closed-cell spray polyurethane foam. The foam should be protected with a thermal barrier (for example, 1/2-in. drywall).
  • Above-grade frame walls can be insulated by blowing dense-packed cellulose into stud cavities through holes drilled through the siding. When insulation is complete, the holes are plugged.
  • If siding is being replaced, rigid foam or spray polyurethane foam can be installed on top of the exterior sheathing. Exterior foam retrofit jobs require considerable trim work around windows and doors, however.
  • Flat ceilings under unconditioned attics are usually easy to insulate with blown-in cellulose.
  • Improving the insulation over a sloped ceiling is often easier from the exterior than the interior. Rigid foam insulation can be added above the roof sheathing in conjunction with new roofing.
After air-sealing and insulation work is complete, the renovated home should be tested for radon. Radon levels often increase after a home has been weatherized.
If a house is undergoing extensive remodeling, it's worth considering a deep energy retrofit.
--
Scott's Contracting
scottscontracting@gmail.com
http://www.stlouisrenewableenergy.com
http://stlouisrenewableenergy.blogspot.com

Insulation and Thermal Performance

Insulation: Thermal Performance is Just the Beginning


InsulSafe ® 4, made by CertainTeed Corporation, is a formaldehyde-free, loose-fill, fiberglass insulation suitable for open-blow attic applications. The product contains recycled glass cullet and carries Greenguard™ certification for low emissions.
We last took a broad look at insulation materials exactly ten years ago: in the January/February 1995 issue. A lot has happened since then—manufacturers have introduced new insulation materials, new product formulations have eliminated problem materials such as HCFCs, and improved understanding of performance and health risks has informed our building practices. But the fundamental issues have not changed over ten years. Insulation remains a critically important component of any green building—whether residential or commercial. No matter the type of insulation used, if it is used appropriately, its environmental benefits over a building's life will almost certainly far outweigh any negatives—and dwarf any environmental differences among the alternative materials.

This article provides a survey of insulation materials, beginning with an examination of what insulation is and how it works. Much of the article focuses on life-cycle considerations for different insulation materials: environmental and health issues associated with resource extraction, manufacture, use, and disposal.

Understanding Insulation

To really understand insulation materials, you have to understand the basics of heat flow. There are three primary mechanisms of heat flow: conduction, convection, and radiation. Thermal conduction is the movement of heat from direct contact: one molecule is activated (excited) by heat and transfers that kinetic energy to an adjacent molecule. We generally think of conduction occurring between solid materials—the handle of a hot skillet conducting its heat to your hand, for example—but thermal conduction also occurs with liquids and gases.

Convection is the transfer of heat in liquids and gases by the movement of those molecules from one place to another. As air is warmed, it expands, becomes more buoyant, and rises—a process called natural convection. Forced convection is the distribution of warm air by use of a fan or air handler.
Finally, radiation is the transfer of heat from one body to another via the propagation of electromagnetic waves. A warmer body will radiate heat to a cooler body. When you sit in front of a fireplace and look into the fire, your face is warmed by the radiant transfer of energy from that heat source to your face. That radiant energy is not affected by air currents and occurs even across a vacuum—as we know from lying in the sun!

Most insulation materials function by slowing the conductive flow of heat. Materials with low thermal conductivity more effectively block heat flow than materials with high thermal conductivity. The R-value of an insulation material measures its resistance to heat flow. R-value is the inverse of U-factor, which is a measure of heat transfer, usually measured in Btu/hr·ft 2·°F or W/m 2·°C. Most insulation materials work by trapping tiny pockets of air (or some other gas). The performance of that insulation material is determined primarily by the conductivity of the air, or other gas, in those spaces. If convection is prevented, a 1" (25 mm) air space has a conductivity of about 0.18 Btu/hr·ft 2·°F (1.02 W/m 2·°C). Its resistance to conductive heat loss, the inverse of that value, is R-5.5 per inch (RSI-38/m). With fiber insulation materials, such as fiberglass, cellulose, and cotton, pockets of air are trapped between the fibers. With cellular insulation materials, such as polystyrene, polyisocyanurate (polyiso), and polyurethane, the air—or other gas—is trapped within the plastic cells comprising the foam.

While resistance to conductive heat flow is the primary operative property of insulation materials, convection and radiation can come into play as well. With polyiso insulation, for example, according to Richard Roe of the Atlas Roofing Corporation in an August 2002 article in Interface magazine, 60–65% of the heat transfer is attributed to the conductivity of the blowing agent gases trapped in the cells, while 20–25% is attributed to the thermal conductivity of the solid polymer matrix, and 10–15% is attributed to radiation. One key design features of an insulation material is keeping the air pockets small enough to limit convection within those spaces and radiation across those spaces. With fiber insulation materials, the fibers have to be packed densely enough to effectively stop airflow through the material. (Air blowing through the insulation would carry heat by convection.)

With insulation materials that incorporate radiant barriers (foil-faced batt insulation, radiant-barrier bubble-pack insulation, and reflective barriers on rigid foam sheathing), the reflective surface functions by reducing radiant heat transfer. To function in this capacity, the reflective surface has to be next to an air space. The surface may function by reflecting heat radiation or (more commonly) by emitting less radiant energy from it. This is why a radiant barrier can reduce heat loss even when the reflective (low-emissivity) surface is facing the cold side.

Note that air leakage is a type of convection. Air leakage allows conditioned air to leak out of a building and unconditioned air to leak in—bypassing the insulated portions of the envelope. In older homes air leakage around windows, through poorly fitting doors, and across poorly detailed walls can sometimes account for over half of the total wintertime heat loss! Air leakage can also occur through an insulation material, which can reduce that material's effective R-value. Loose-fill fiberglass, for example, usually allows more airflow than does cellulose insulation.

Life-Cycle Considerations with Insulation Materials

In this portion of the article, we examine the four primary life-cycle stages of any building material: raw material acquisition; manufacturing; the use phase, including indoor air quality concerns; and end-of-life disposal and recyclability. In each of these life-cycle stages we highlight key differences among insulation materials and discuss recent developments. Summaries of the key life-cycle considerations are presented by insulation material in the accompanying table.

Raw material acquisition


All Johns Manville fiberglass insulation is now produced with formaldehyde-free binders.
Fiberglass. The most prevalent type of insulation in North America, fiberglass is produced from silica sand with various additives, including boron. Most fiberglass also contains a fairly high percentage of recycled glass. The recycled content can be pre-consumer (post-industrial) glass cullet from float-glass manufacture or post-consumer glass collected through bottle recycling programs. In 2003 the fiberglass insulation industry used 1.1 billion pounds (500 million kg) of recycled glass, according to the North American Insulation Manufacturers Association (NAIMA), though the industry-wide split between pre-consumer and post-consumer recycled glass is not available. According to Robin Bectel of NAIMA, fiberglass insulation represents the second-largest market for recycled bottle glass (after the packaging industry).

Most U.S. fiberglass insulation has a minimum 20–30% recycled content. Owens Corning, for example, has been third-party certified by Scientific Certification Systems (SCS) to contain at least 30% recycled content—4% post-consumer and 26% pre-consumer, according to Jim Worden of the company. Johns Manville has an SCS-certified minimum recycled content of 25%; CertainTeed claims a minimum recycled content of 20–25% to meet U.S. Environmental Protection Agency (EPA) requirements under the Comprehensive Procurement Guidelines (CPG); and Knauf Fiberglass claims a minimum 20% recycled content, all of it post-consumer. Recycled-content information for Guardian Fiberglass was not available.

Mineral wool. Mineral wool is made from both iron ore blast-furnace slag (an industrial waste product from steel production) and rock such as basalt. In 2003 the mineral-slag wool industry used 514 million pounds (233 million kg) of slag. This is down 45% from the slag use in 1992. Mineral-slag wool production is down in part because building codes are shifting away from the passive fire resistance that mineral wool provides toward active sprinklering of buildings.

Cellulose. Cellulose insulation is made primarily from post-consumer recycled newspaper, with up to 20% ammonium sulfate and/or borate flame retardants. While cellulose insulation used to be one of the highest-value uses of old newspaper, today dozens of de-inking plants in North America turn old newspaper into new newsprint. Producing cellulose insulation from old newspaper can be referred to as downcycling; from an environmental standpoint, turning a waste product back into a new form of the same material is preferable to turning it into a lower-grade material. (Note that producing fiberglass insulation from beverage bottles or glass cullet is also downcycling.)


Plastic foam insulation. Plastic foam insulation materials, including extruded polystyrene (XPS), expanded polystyrene (EPS), polyisocyanurate, and the various types of spray polyurethane insulation, are all produced primarily from petrochemicals. Both natural gas and petroleum are common feedstocks, and both have significant environmental impacts associated with their extraction, refining, and transport.
At least two open-cell, spray polyurethane insulation products are manufactured in part from soybeans. Two-component BioBase 501 (see EBN Vol. 12, No. 9) and HealthySeal 500 are produced with soy oil comprising approximately 40% of the polyol component. (Polyurethanes are produced by reacting an isocyanate with a polyol, which is a type of alcohol.) The resultant polyurethane foam ends up being about 25% soy-derived and 75% petrochemical-derived.


Polystyrene. Recycled polystyrene can be incorporated into polystyrene foam insulation fairly easily, since polystyrene is a thermoplastic. At least one EPS insulation product contains recycled polystyrene: Polar 10 from Polar Industries is made with up to 40–60% post-industrial recycled content (see EBN Vol. 10, No. 2). The only XPS product that includes recycled content today is Owens Corning Foamular®, which is SCS-certified to contain a minimum of 15% pre-consumer recycled polystyrene.


Polyisocyanurate. Polyiso insulation incorporates a relatively small amount (9–10%) of recycled content to comply with CPG minimums. A portion of the polyol used in polyiso is produced from recycled PET bottles. The polyiso industry is one of the largest users of recycled, mixed-color PET bottles, according to the Polyisocyanurate Insulation Manufacturers Association (PIMA). The foil facings on many polyiso boardstock products may also contain some recycled content.

Bonded Logic's cotton insulation is manufactured from pre-consumer recycled denim waste.


Cotton insulation. Cotton insulation is made today by two manufacturers. Bonded Logic, Inc. and Inno-Therm, Inc. make batt insulation products from pre-consumer recycled denim scrap. The cotton or cotton-polyester fibers are treated with a nonhalogenated flame retardant. UltraTouch, produced by Bonded Logic, contains approximately 85% pre-consumer recycled fiber saturated with borate flame retardants to provide fire resistance. Inno-Therm is believed to be using a mix of borate and ammonium sulfate flame retardants. In addition to its use in batt insulation products, cotton insulation is used by Payless Insulation, Inc. in insulated flexible duct products; Bonded Logic supplies the cotton insulation for these products.


Cementitious foam insulation. The totally inorganic, cementitious Air Krete ® is produced from magnesium oxide, derived from seawater, and from a ceramic talc mined in Governor, New York. While essentially the same material as it was when last covered in EBN ( Vol. 6, No. 7), Air Krete has undergone some modest refinements, according to vice-president Bruce Christopher. "We have continued to improve both the product and the equipment for installation," he told EBN. But he noted that friability—the fragility of the cured foam—remains their biggest challenge. "If there is a downside to Air Krete, it's its friability." Despite its resistance to the idea, the company may decide to add a little plastic to make it less friable, said Christopher. The challenge in adding plastic would be maintaining the superb fire resistance of the insulation material. While cost is highly variable, depending on location, size of the job, and other factors, it averages 30–50¢ per board foot, according to Christopher.
Air Krete remains a very good alternative to another foamed-in-place insulation material used primarily for insulating masonry block, Tripolymer ® foam, produced by the C. P. Chemical Company. Tripolymer foam is a foamed phenol-formaldehyde insulation—a material that some manufacturers of urea-formaldehyde foam insulation (UFFI) switched to after formaldehyde emissions from UFFI led to its discontinuance in the 1970s.


Radiant barriers. Radiant barriers could be produced with recycled aluminum, but this is rarely if ever done, because very pure aluminum is needed to achieve the thin foils. Recycled polyethylene, however, can be used for the foam that is sometimes used with radiant barriers. Low-E ® Insulation, produced by Environmentally Safe Products, Inc., uses polyethylene foam with 40% post-consumer recycled content. In its TempShield™ radiant insulation product, Sealed Air Corporation uses 20% recycled-content cellular polyethylene for the insulation laminated between layers of reflective foil. A number of manufactured panel products have reflective facings glued to one side.

Manufacturing and transport

Fiberglass. Fiberglass insulation is manufactured with binders (typically phenol-formaldehyde) that hold the glass fibers together. The only fiberglass insulation material that did not contain a binder, Owens Corning's Miraflex™ (see EBN Vol. 4, No. 1) was pulled off the market late in 2004. Manufacture of Miraflex was actually discontinued at the beginning of 2003, according to Gale Tedhams, Owens Corning's product manager for residential insulation, but enough material had been stockpiled to sell it through 2004—mostly through Lowe's stores. "It just had a very limited market," Tedhams told EBN. Owens Corning did not promote the health benefits of not having a binder but focused on the packaging benefits—rolls of the insulation take up half the space of standard fiberglass. While the product carried a "slight price premium," according to Tedhams, it was "very expensive to manufacture." See additional discussion of binders used in fiberglass insulation under "Use phase and IAQ concerns."


Cellulose. Because cellulose is inherently combustible, flame retardants are required to make it an acceptable material for building insulation. As has been the case for the past ten years, the primary flame retardants used in cellulose insulation are ammonium sulfate, borax, and boric acid. According to Daniel Lea, executive director of the Cellulose Insulation Manufacturers Association (CIMA), these additives are typically used in combination, though a few manufacturers offer products that use all-borate retardants.


Polyisocyanurate. The biggest environmental news in foam boardstock insulation has been the elimination of HCFC-141b in polyiso. The industry completed the transition from that ozone-depleting compound to the blowing agent pentane at the end of 2002. (Some manufacturers continued using stockpiled HCFC-141b in early 2003 while plant modifications were completed.) The transition to an ozone-safe formulation was a big step for polyiso, and it renders the product significantly better environmentally than extruded polystyrene (XPS), which in North America is still made with an HCFC blowing agent.
In an industry that is generally slow to change, these changes in polyiso have been dramatic. In 1992 polyiso was all produced with CFC-11. By mid-1993 the polyiso industry had shifted completely to HCFC-141b, which has only about 10% the ozone depletion potential of CFC-11. Atlas Industries then led the transition away from HCFCs, introducing its ozone-friendly AC-Ultra™ in February 1998 (see EBN Vol. 7, No. 5). By May 2001 the company had fully converted three of its plants to pentane (see EBN Vol. 10, No. 5), with others converted early in 2002.


Polystyrene. Polystyrene has some fairly troubling chemical precursors in its production. The polystyrene used in both XPS and EPS is made by reacting ethylene (from natural gas or crude oil) with benzene (from crude oil, via naphtha catalytic reforming) to produce ethyl-benzene. The ethyl-benzene is converted into vinyl-benzene or styrene monomer, which is then polymerized into polystyrene. Benzene is listed in the 10th Report on Carcinogens, put out by the National Toxicology Program of the U.S. Department of Health and Human Services, as a "known carcinogen." The International Agency for Research on Cancer (IARC) of the World Health Organization lists benzene as a "confirmed human carcinogen" and styrene monomer as a "possible human carcinogen." Some material safety data sheets (MSDS) for polystyrene list residual styrene monomer as a constituent of the foam at levels up to 0.2%. While benzene is also used in polyiso and polyurethane production, these insulation materials are less likely than polystyrene to contain residual toxic chemicals.


Extruded polystyrene. XPS and EPS differ in how the foam is expanded—and they use quite different blowing agents. EPS has long been made with non-ozone-depleting pentane, but XPS still relies on HCFCs. Though the XPS industry led the charge in replacing CFCs with far-less-damaging HCFCs, it is today the only type of boardstock insulation that remains harmful to stratospheric ozone. Amofoam (now Pactiv) was the first company to switch from CFC-12 to HCFC-142b, in 1990, and the entire XPS industry completed that transition in 1992. The transition away from HCFC-142b is not likely in the U.S. until close to the 2010 EPA deadline for doing so (see EBN Vol. 11, No. 7), according to Worden at Owens Corning. While European manufacturers of XPS shifted to either HFC-134A or carbon dioxide in 2002, more stringent energy standards and different construction systems in North America make the same sort of conversion more difficult here, says Worden. European XPS is a higher-density product with a lower R-value.


Expanded polystyrene. Expanded polystyrene (EPS) continues to be made with non-ozone-depleting pentane as the expanding agent. Some manufacturers are using a low-pentane formulation that results in lower pentane emissions. (While not an ozone-depleting compound, pentane can generate ground-level smog.) The more distributed production of EPS, compared with XPS, may reduce shipping energy consumption to some extent.


Flame retardants and polystyrene. All foam plastic insulation materials rely on flame retardants to meet fire-resistance standards. EPS and XPS are produced using the brominated flame retardant HBCD (hexabromocyclododecane) at concentrations of 0.5–2.0% by weight. HBCD is not the focus of as much attention as another class of brominated flame retardants (PBDEs), but some evidence indicates that it is more bioaccumulative than PBDEs and just as likely to be toxic to humans (see EBN Vol. 13, No. 6).


Flame retardants and polyisocyanurate. Ironically, until recently flame retardants were not used in most polyiso insulation. With HCFC blowing agents, this thermoset plastic foam was able to achieve the required Class I fire ratings without any added flame retardant. But with the substitution of pentane blowing agents for HCFC-141b, manufacturers now must add flame retardants. Although manufacturers rarely divulge their formulations (and can apparently get around the requirement to list the flame retardant in the MSDS because it is part of one component or the other (the polyol or isocyanate), the most common flame retardant used in polyiso today is believed to be TCPP (tris(chloropropyl) phosphate), a compound that relies on both phosphorous and chlorine as the fire-retarding components. The typical concentration in the foam insulation is 5–14% by weight. While a halogenated compound, TCPP is much less likely to be a persistent bioaccumulative toxin than HBCD, according to the PBT Profiler software from EPA.


Spray polyurethane. While polyiso manufacturers had to eliminate their use of HCFC-141b by January 1, 2003, manufacturers of closed-cell (high-density) spray polyurethane were given an extension for the transition to non-ozone-depleting blowing agents. HCFC-141b for spray polyurethane cannot be sold after December 31, 2004, though polyurethane installers can use inventoried HCFC-based chemicals until July 1, 2005, according to Ken Gayer, the global business manager for foam blowing agents at Honeywell Specialty Materials, which produces the non-ozone-depleting blowing agent HFC-245fa under the tradename Enovate 3000.
Most spray polyurethane companies are converting to Honeywell's HFC-245fa. While significantly more expensive than HCFC-141b, the resultant foam achieves similar energy performance. The ozone depletion potential of HFC-245fa is zero, but the global warming potential is similar to that of HCFC-141b. Hydrocarbon blowing agents are avoided with spray polyurethane because of flammability concerns and difficulties with the vapor pressure, according to Gayer.


Low-density, open-cell polyurethane produced by Icynene is material- efficient and uses water as the blowing agent.
Open-cell polyurethane, including the products made by Icynene, Inc. and Demilec, Inc. as well as the newer soy-based foams, are produced with water as the blowing agent. They do not achieve R-values as high as those of closed-cell polyurethane, but they are more resource-efficient, using just one-fourth to one-third the material used for a comparable volume of closed-cell polyurethane.

Flame retardants and spray polyurethane. Both closed-cell (high-density) and open-cell (low-density) polyurethane insulation contain flame retardants, but these are non-brominated flame retardants. While manufacturers are reluctant to share this information, the best available information indicates that the two flame retardants most commonly used in spray polyurethane are TCPP, which contains chlorine but not bromine, and RDP (resorcinol-bis-diphenylphosphate), which is totally halogen-free.

Use phase and IAQ concerns

Fiberglass and mineral wool. Concerns about mineral and glass fibers possibly being carcinogenic have been widely publicized over the past ten years—especially by competing industries. These concerns resulted in cancer warning labels being required for most products, but more recently these concerns are waning. In October 2001, IARC changed its classification for fiberglass and mineral wool from "possible human carcinogen" to "not a known human carcinogen." This change has allowed mineral wool (slag wool and rock wool) manufacturers to drop the warning labels.
Fiberglass insulation continues to carry the cancer warnings because, in addition to the IARC listing, the National Toxicology Program added glass fibers to its Report on Carcinogens in 1990. According to Angus Crane, the vice president and general council for NAIMA, glass fibers were added to the NTP possible-carcinogen list because of the IARC-reported studies. Now that IARC has dropped the possible-carcinogen listing for glass fibers, the material is likely to be dropped from the NTP list. NAIMA has petitioned NTP to delist glass fibers, but that process typically takes several years. Crane hopes to see the listing removed in late 2005 or early 2006. If and when that happens, the industry will petition the State of California to remove the requirement under Proposition 65 that fiberglass insulation products include a warning about cancer.
Meanwhile, the carcinogenicity of formaldehyde, which could be released in very small quantities from the phenol-formaldehyde binder used in most fiberglass insulation, has recently been upgraded. In June 2004, IARC changed its classification of formaldehyde from a "probable human carcinogen" to a "confirmed human carcinogen." Most of this binder is volatized and dissipated during a baking stage of the manufacturing process, but residual formaldehyde may remain in the product. Johns Manville, one of the five major producers of fiberglass insulation in North America, switched to 100% acrylic binder for its fiberglass insulation product line in 2002 (see EBN Vol. 11, No. 3). The other major fiberglass insulation manufacturers have all had their products certified as low-emitting by Greenguard™.


Mineral wool. For cavity-fill and attic applications, rock wool and slag wool are similar to fiberglass in look and feel, though the density is greater and the sound control better. The fire resistance of mineral wool is also significantly better than that of fiberglass, because of both the higher density and the significantly higher temperatures required for melting. While these fire-resistance properties used to be a major selling point, greater reliance on sprinklers in buildings, rather than passive fire resistance, is resulting in decreased use of mineral wool, according to Crane of NAIMA.
For below-grade applications, one rigid mineral-wool product, Roxul drainboard, offers superb performance, owing to its hydrophobic properties and its excellent drainage characteristics (see EBN Vol. 4, No. 6). This material has never been actively marketed in the U.S., but Roxul products in general are becoming more widely available here.


Cellulose. Cellulose insulation has never been required to carry indoor air quality warnings, and the fiberglass and mineral wool industries remain upset that their products have come under greater scrutiny than cellulose. "Our competitors have not gone through the testing," said Angus Crane of NAIMA. "It is dangerous to assume that an untested material is safe," he told EBN. The editors at EBN continue to take the position that all fiber insulation products (fiberglass, mineral wool, and cellulose) are safe if properly installed, and we would much prefer to see insulation manufacturers focus on the positive benefits of all insulation, rather than potential risks of their competitors' products. The health concerns with cellulose range from inhalation of dust during installation to VOC emissions from printing inks (which are now almost entirely vegetable-based) and limited evidence of toxicity of boric acid flame retardants. For more on health issues with cellulose insulation see EBN Vol. 2, No. 5.

As for installation and performance, cellulose insulation has evolved considerably over the past 20 years. According to Daniel Lea of CIMA, the average installed density of cellulose insulation has dropped from 2.6 pounds per cubic foot (42 kg/m 3) in 1984 to 1.6 pcf (26 kg/m 3) today. "R for R, today's cellulose insulation products are almost 40% lighter than those of 1984," said Lea. Most cellulose insulation today is being installed as "cellulose wall-cavity spray," a process that has sometimes been referred to as "wet-spray" cellulose. CIMA is trying to discourage the use of the term wet-spray because it implies a process that is far wetter than is the case. "I think there is a perception that the material is applied almost as a fibrous papier-mâché," said Lea. "That is far from the case; if you were to touch wall spray seconds after it's applied, you probably couldn't tell that water was added during the installation process," he said. The typical installed moisture content today is 30–35%, according to Lea, while a moisture content as high as 60% was not uncommon 15 years ago.


Fiber insulation installation. Quality dust masks or respirators should be used while installing fiberglass, mineral wool, and cellulose. (Cotton insulation is the only fiber insulation material that can be installed safely without protective measures.) Building design and detailing should ensure that fibers cannot enter forced-air distribution or ventilation systems. Airtight construction practices should be used to ensure that fiber insulation stays where it was installed.


Polystyrene. Indoor air quality concerns with XPS and EPS are similar to concerns addressed previously relating to manufacturing: the potential release of residual styrene monomer and flame retardants. The brominated flame retardants used in polystyrene present a greater health concern than the nonbrominated flame retardants used in polyisocyanurate, spray polyurethane, and cellulose insulation.


Polyisocyanurate. Now that polyiso is no longer produced with HCFCs, it is the environmentally preferred rigid boardstock insulation for above-grade applications. (Polyiso is not recommended for below-grade applications because it can absorb moisture.) Polyiso manufacturers disagree as to whether rigid foam produced today with hydrocarbon blowing agents achieves an R-value comparable to that of the older material made with HCFC-141b. The conductivity of the hydrocarbon blowing agent is higher than that of HCFC-141b, and this has led Dow Chemical to downgrade the rated R-values for all of its polyiso insulation, including Thermax ®. However, Richard Roe of Atlas Roofing argues that the smaller cell size of foam produced with hydrocarbon blowing agents, the slower diffusion rate of the hydrocarbon out of the polymer cells, and the lower absorption of the hydrocarbon blowing agent by the polymer collectively result in better long-term R-value stability.
Most polyiso manufacturers are now using new long-term thermal resistance (LTTR) values for reporting aged R-values. This method was adopted in Canada in mid-2002 and in the U.S. in January 2003. This method produces 5-year aged R-values that are lower than the 6-month aged R-values that had previously been reported. The bottom line is that the rated long-term stabilized R-value of polyiso is now between R-6 and 6.5 per inch (RSI-42 to 45 per meter), depending on thickness and facings.


Closed-cell polyurethane. Closed-cell, high-density polyurethane is a very good performer owing to the low-conductivity gas in the cellular structure. It is used both for cavity installation and as an insulating roofing material, which is typically referred to as spray polyurethane foam or SPF. The closed-cell structure gives SPF structural properties. There should be no significant impact on R-value with the shift to non-ozone-depleting HFC-245fa blowing agent, which is becoming the industry standard. Polyurethane also exhibits superb adhesive properties and good compressive strength.


Open-cell polyurethane. Open-cell polyurethane is most commonly installed into open cavities, though formulations are available for filling closed cavities from holes at the top. This is a nonstructural foam, though these materials seal very well, and their flexibility allows for some movement of the framing materials as shrinkage and expansion occur. These properties make them very effective insulation materials for older buildings.
Both closed-cell and open-cell polyurethane must be installed by trained professionals. Special care is required to ensure the safety of insulation installers working with these materials; other people should not be in the space while polyurethane insulation is being installed. Once cured, polyurethane insulation is considered by most IAQ experts to be quite inert.

End-of-life reuse and recyclability

Loose-fill and batt insulation. It is difficult to salvage loose-fill or batt insulation and reuse it, though this can be done. Virtually no fiber insulation is recycled after use in buildings—due to contamination with dust and other materials. Scrap insulation generated during installation can be collected and reused quite easily.

Insulation Materials – Summary of Environmental and Health Considerations



Rigid boardstock insulation. Rigid insulation can be salvaged and reused if it is protected during removal. For roof insulation applications, reuse is most feasible when protected-membrane or inverted roof configurations are used (see EBN Vol. 7, No. 10). In this system, a non-water-absorbing rigid insulation, such as XPS, is laid on top of the roof membrane, and ballast is installed on top of the insulation. When re-roofing is required, the insulation can be removed and stored for safekeeping, then reinstalled after the new roof membrane is laid down.

Of the rigid insulation materials, only polystyrene can be recycled. This thermoplastic can be melted and re-expanded into either polystyrene insulation or packaging. Unfortunately, very little polystyrene is being recycled currently. Polyiso and polyurethane cannot be recycled because these foams are thermoset plastics.

Final Thoughts and Recommendations

Insulation is a key component of any green building. More important than the decision of what type of insulation to install is the decision of how much insulation should be installed. From an environmental standpoint, a thicker layer of a relatively nongreen insulation material is almost always better than an inadequate thickness of the greenest insulation material available. This point cannot be over-emphasized.

However, assuming that adequate R-values can be achieved, choosing a green insulation material over a nongreen one can be a very good decision. The accompanying table should help to identify materials that meet your needs and satisfy the environmental priorities of your project.

Summary recommendations:

• Provide the highest feasible insulation levels.
• With lower R-value materials, increase insulation thickness.
• Avoid extruded polystyrene due to the ozone-depletion potential of blowing agent.
• Except where moisture may be an issue, use polyiso instead of either XPS or EPS.
• Rigid mineral wool, such as that made by Roxul, is a very good foundation insulation material due to its superb drainage properties.
• With highly conductive framing systems, especially steel, minimize thermal bridging by wrapping the frame with a layer of rigid board insulation.
• Choose high-recycled-content insulation materials when doing so will not result in significant loss of R-value compared with other materials.
• With roof insulation, consider a protected-membrane roof so that insulation can be reused.
• Address air leakage and moisture resistance in insulation detailing. A good source of information on building science issues is http://www.buildingscience.com/.
• For chemically sensitive individuals, test potential insulation materials for reaction before installation.
• Choose an insulation contractor who recycles scrap insulation.

Insulation and Thermal Performance

Insulation: Thermal Performance is Just the Beginning


InsulSafe ® 4, made by CertainTeed Corporation, is a formaldehyde-free, loose-fill, fiberglass insulation suitable for open-blow attic applications. The product contains recycled glass cullet and carries Greenguard™ certification for low emissions.
We last took a broad look at insulation materials exactly ten years ago: in the January/February 1995 issue. A lot has happened since then—manufacturers have introduced new insulation materials, new product formulations have eliminated problem materials such as HCFCs, and improved understanding of performance and health risks has informed our building practices. But the fundamental issues have not changed over ten years. Insulation remains a critically important component of any green building—whether residential or commercial. No matter the type of insulation used, if it is used appropriately, its environmental benefits over a building's life will almost certainly far outweigh any negatives—and dwarf any environmental differences among the alternative materials.
This article provides a survey of insulation materials, beginning with an examination of what insulation is and how it works. Much of the article focuses on life-cycle considerations for different insulation materials: environmental and health issues associated with resource extraction, manufacture, use, and disposal.

Understanding Insulation

To really understand insulation materials, you have to understand the basics of heat flow. There are three primary mechanisms of heat flow: conduction, convection, and radiation. Thermal conduction is the movement of heat from direct contact: one molecule is activated (excited) by heat and transfers that kinetic energy to an adjacent molecule. We generally think of conduction occurring between solid materials—the handle of a hot skillet conducting its heat to your hand, for example—but thermal conduction also occurs with liquids and gases.
Convection is the transfer of heat in liquids and gases by the movement of those molecules from one place to another. As air is warmed, it expands, becomes more buoyant, and rises—a process called natural convection. Forced convection is the distribution of warm air by use of a fan or air handler.

Finally, radiation is the transfer of heat from one body to another via the propagation of electromagnetic waves. A warmer body will radiate heat to a cooler body. When you sit in front of a fireplace and look into the fire, your face is warmed by the radiant transfer of energy from that heat source to your face. That radiant energy is not affected by air currents and occurs even across a vacuum—as we know from lying in the sun!

Most insulation materials function by slowing the conductive flow of heat. Materials with low thermal conductivity more effectively block heat flow than materials with high thermal conductivity. The R-value of an insulation material measures its resistance to heat flow. R-value is the inverse of U-factor, which is a measure of heat transfer, usually measured in Btu/hr·ft 2·°F or W/m 2·°C. Most insulation materials work by trapping tiny pockets of air (or some other gas). The performance of that insulation material is determined primarily by the conductivity of the air, or other gas, in those spaces. If convection is prevented, a 1" (25 mm) air space has a conductivity of about 0.18 Btu/hr·ft 2·°F (1.02 W/m 2·°C). Its resistance to conductive heat loss, the inverse of that value, is R-5.5 per inch (RSI-38/m). With fiber insulation materials, such as fiberglass, cellulose, and cotton, pockets of air are trapped between the fibers. With cellular insulation materials, such as polystyrene, polyisocyanurate (polyiso), and polyurethane, the air—or other gas—is trapped within the plastic cells comprising the foam.

While resistance to conductive heat flow is the primary operative property of insulation materials, convection and radiation can come into play as well. With polyiso insulation, for example, according to Richard Roe of the Atlas Roofing Corporation in an August 2002 article in Interface magazine, 60–65% of the heat transfer is attributed to the conductivity of the blowing agent gases trapped in the cells, while 20–25% is attributed to the thermal conductivity of the solid polymer matrix, and 10–15% is attributed to radiation. One key design features of an insulation material is keeping the air pockets small enough to limit convection within those spaces and radiation across those spaces. With fiber insulation materials, the fibers have to be packed densely enough to effectively stop airflow through the material. (Air blowing through the insulation would carry heat by convection.)

With insulation materials that incorporate radiant barriers (foil-faced batt insulation, radiant-barrier bubble-pack insulation, and reflective barriers on rigid foam sheathing), the reflective surface functions by reducing radiant heat transfer. To function in this capacity, the reflective surface has to be next to an air space. The surface may function by reflecting heat radiation or (more commonly) by emitting less radiant energy from it. This is why a radiant barrier can reduce heat loss even when the reflective (low-emissivity) surface is facing the cold side.
Note that air leakage is a type of convection. Air leakage allows conditioned air to leak out of a building and unconditioned air to leak in—bypassing the insulated portions of the envelope. In older homes air leakage around windows, through poorly fitting doors, and across poorly detailed walls can sometimes account for over half of the total wintertime heat loss! Air leakage can also occur through an insulation material, which can reduce that material's effective R-value. Loose-fill fiberglass, for example, usually allows more airflow than does cellulose insulation.

Life-Cycle Considerations with Insulation Materials

In this portion of the article, we examine the four primary life-cycle stages of any building material: raw material acquisition; manufacturing; the use phase, including indoor air quality concerns; and end-of-life disposal and recyclability. In each of these life-cycle stages we highlight key differences among insulation materials and discuss recent developments. Summaries of the key life-cycle considerations are presented by insulation material in the accompanying table.

Raw material acquisition


All Johns Manville fiberglass insulation is now produced with formaldehyde-free binders.
Fiberglass. The most prevalent type of insulation in North America, fiberglass is produced from silica sand with various additives, including boron. Most fiberglass also contains a fairly high percentage of recycled glass. The recycled content can be pre-consumer (post-industrial) glass cullet from float-glass manufacture or post-consumer glass collected through bottle recycling programs. In 2003 the fiberglass insulation industry used 1.1 billion pounds (500 million kg) of recycled glass, according to the North American Insulation Manufacturers Association (NAIMA), though the industry-wide split between pre-consumer and post-consumer recycled glass is not available. According to Robin Bectel of NAIMA, fiberglass insulation represents the second-largest market for recycled bottle glass (after the packaging industry).

Most U.S. fiberglass insulation has a minimum 20–30% recycled content. Owens Corning, for example, has been third-party certified by Scientific Certification Systems (SCS) to contain at least 30% recycled content—4% post-consumer and 26% pre-consumer, according to Jim Worden of the company. Johns Manville has an SCS-certified minimum recycled content of 25%; CertainTeed claims a minimum recycled content of 20–25% to meet U.S. Environmental Protection Agency (EPA) requirements under the Comprehensive Procurement Guidelines (CPG); and Knauf Fiberglass claims a minimum 20% recycled content, all of it post-consumer. Recycled-content information for Guardian Fiberglass was not available.

Mineral wool. Mineral wool is made from both iron ore blast-furnace slag (an industrial waste product from steel production) and rock such as basalt. In 2003 the mineral-slag wool industry used 514 million pounds (233 million kg) of slag. This is down 45% from the slag use in 1992. Mineral-slag wool production is down in part because building codes are shifting away from the passive fire resistance that mineral wool provides toward active sprinklering of buildings.
Cellulose. Cellulose insulation is made primarily from post-consumer recycled newspaper, with up to 20% ammonium sulfate and/or borate flame retardants. While cellulose insulation used to be one of the highest-value uses of old newspaper, today dozens of de-inking plants in North America turn old newspaper into new newsprint. Producing cellulose insulation from old newspaper can be referred to as downcycling; from an environmental standpoint, turning a waste product back into a new form of the same material is preferable to turning it into a lower-grade material. (Note that producing fiberglass insulation from beverage bottles or glass cullet is also downcycling.)

Plastic foam insulation. Plastic foam insulation materials, including extruded polystyrene (XPS), expanded polystyrene (EPS), polyisocyanurate, and the various types of spray polyurethane insulation, are all produced primarily from petrochemicals. Both natural gas and petroleum are common feedstocks, and both have significant environmental impacts associated with their extraction, refining, and transport.

At least two open-cell, spray polyurethane insulation products are manufactured in part from soybeans. Two-component BioBase 501 (see EBN Vol. 12, No. 9) and HealthySeal 500 are produced with soy oil comprising approximately 40% of the polyol component. (Polyurethanes are produced by reacting an isocyanate with a polyol, which is a type of alcohol.) The resultant polyurethane foam ends up being about 25% soy-derived and 75% petrochemical-derived.

Polystyrene. Recycled polystyrene can be incorporated into polystyrene foam insulation fairly easily, since polystyrene is a thermoplastic. At least one EPS insulation product contains recycled polystyrene: Polar 10 from Polar Industries is made with up to 40–60% post-industrial recycled content (see EBN Vol. 10, No. 2). The only XPS product that includes recycled content today is Owens Corning Foamular®, which is SCS-certified to contain a minimum of 15% pre-consumer recycled polystyrene.

Polyisocyanurate. Polyiso insulation incorporates a relatively small amount (9–10%) of recycled content to comply with CPG minimums. A portion of the polyol used in polyiso is produced from recycled PET bottles. The polyiso industry is one of the largest users of recycled, mixed-color PET bottles, according to the Polyisocyanurate Insulation Manufacturers Association (PIMA). The foil facings on many polyiso boardstock products may also contain some recycled content.

Bonded Logic's cotton insulation is manufactured from pre-consumer recycled denim waste.
Cotton insulation. Cotton insulation is made today by two manufacturers. Bonded Logic, Inc. and Inno-Therm, Inc. make batt insulation products from pre-consumer recycled denim scrap. The cotton or cotton-polyester fibers are treated with a nonhalogenated flame retardant. UltraTouch, produced by Bonded Logic, contains approximately 85% pre-consumer recycled fiber saturated with borate flame retardants to provide fire resistance. Inno-Therm is believed to be using a mix of borate and ammonium sulfate flame retardants. In addition to its use in batt insulation products, cotton insulation is used by Payless Insulation, Inc. in insulated flexible duct products; Bonded Logic supplies the cotton insulation for these products.

Cementitious foam insulation. The totally inorganic, cementitious Air Krete ® is produced from magnesium oxide, derived from seawater, and from a ceramic talc mined in Governor, New York. While essentially the same material as it was when last covered in EBN ( Vol. 6, No. 7), Air Krete has undergone some modest refinements, according to vice-president Bruce Christopher. "We have continued to improve both the product and the equipment for installation," he told EBN. But he noted that friability—the fragility of the cured foam—remains their biggest challenge. "If there is a downside to Air Krete, it's its friability." Despite its resistance to the idea, the company may decide to add a little plastic to make it less friable, said Christopher. The challenge in adding plastic would be maintaining the superb fire resistance of the insulation material. While cost is highly variable, depending on location, size of the job, and other factors, it averages 30–50¢ per board foot, according to Christopher.

Air Krete remains a very good alternative to another foamed-in-place insulation material used primarily for insulating masonry block, Tripolymer ® foam, produced by the C. P. Chemical Company. Tripolymer foam is a foamed phenol-formaldehyde insulation—a material that some manufacturers of urea-formaldehyde foam insulation (UFFI) switched to after formaldehyde emissions from UFFI led to its discontinuance in the 1970s.

Radiant barriers. Radiant barriers could be produced with recycled aluminum, but this is rarely if ever done, because very pure aluminum is needed to achieve the thin foils. Recycled polyethylene, however, can be used for the foam that is sometimes used with radiant barriers. Low-E ® Insulation, produced by Environmentally Safe Products, Inc., uses polyethylene foam with 40% post-consumer recycled content. In its TempShield™ radiant insulation product, Sealed Air Corporation uses 20% recycled-content cellular polyethylene for the insulation laminated between layers of reflective foil. A number of manufactured panel products have reflective facings glued to one side.

Manufacturing and transport

Fiberglass. Fiberglass insulation is manufactured with binders (typically phenol-formaldehyde) that hold the glass fibers together. The only fiberglass insulation material that did not contain a binder, Owens Corning's Miraflex™ (see EBN Vol. 4, No. 1) was pulled off the market late in 2004. Manufacture of Miraflex was actually discontinued at the beginning of 2003, according to Gale Tedhams, Owens Corning's product manager for residential insulation, but enough material had been stockpiled to sell it through 2004—mostly through Lowe's stores. "It just had a very limited market," Tedhams told EBN. Owens Corning did not promote the health benefits of not having a binder but focused on the packaging benefits—rolls of the insulation take up half the space of standard fiberglass. While the product carried a "slight price premium," according to Tedhams, it was "very expensive to manufacture." See additional discussion of binders used in fiberglass insulation under "Use phase and IAQ concerns."

Cellulose. Because cellulose is inherently combustible, flame retardants are required to make it an acceptable material for building insulation. As has been the case for the past ten years, the primary flame retardants used in cellulose insulation are ammonium sulfate, borax, and boric acid. According to Daniel Lea, executive director of the Cellulose Insulation Manufacturers Association (CIMA), these additives are typically used in combination, though a few manufacturers offer products that use all-borate retardants.

Polyisocyanurate. The biggest environmental news in foam boardstock insulation has been the elimination of HCFC-141b in polyiso. The industry completed the transition from that ozone-depleting compound to the blowing agent pentane at the end of 2002. (Some manufacturers continued using stockpiled HCFC-141b in early 2003 while plant modifications were completed.) The transition to an ozone-safe formulation was a big step for polyiso, and it renders the product significantly better environmentally than extruded polystyrene (XPS), which in North America is still made with an HCFC blowing agent.

In an industry that is generally slow to change, these changes in polyiso have been dramatic. In 1992 polyiso was all produced with CFC-11. By mid-1993 the polyiso industry had shifted completely to HCFC-141b, which has only about 10% the ozone depletion potential of CFC-11. Atlas Industries then led the transition away from HCFCs, introducing its ozone-friendly AC-Ultra™ in February 1998 (see EBN Vol. 7, No. 5). By May 2001 the company had fully converted three of its plants to pentane (see EBN Vol. 10, No. 5), with others converted early in 2002.

Polystyrene. Polystyrene has some fairly troubling chemical precursors in its production. The polystyrene used in both XPS and EPS is made by reacting ethylene (from natural gas or crude oil) with benzene (from crude oil, via naphtha catalytic reforming) to produce ethyl-benzene. The ethyl-benzene is converted into vinyl-benzene or styrene monomer, which is then polymerized into polystyrene. Benzene is listed in the 10th Report on Carcinogens, put out by the National Toxicology Program of the U.S. Department of Health and Human Services, as a "known carcinogen." The International Agency for Research on Cancer (IARC) of the World Health Organization lists benzene as a "confirmed human carcinogen" and styrene monomer as a "possible human carcinogen." Some material safety data sheets (MSDS) for polystyrene list residual styrene monomer as a constituent of the foam at levels up to 0.2%. While benzene is also used in polyiso and polyurethane production, these insulation materials are less likely than polystyrene to contain residual toxic chemicals.

Extruded polystyrene. XPS and EPS differ in how the foam is expanded—and they use quite different blowing agents. EPS has long been made with non-ozone-depleting pentane, but XPS still relies on HCFCs. Though the XPS industry led the charge in replacing CFCs with far-less-damaging HCFCs, it is today the only type of boardstock insulation that remains harmful to stratospheric ozone. Amofoam (now Pactiv) was the first company to switch from CFC-12 to HCFC-142b, in 1990, and the entire XPS industry completed that transition in 1992. The transition away from HCFC-142b is not likely in the U.S. until close to the 2010 EPA deadline for doing so (see EBN Vol. 11, No. 7), according to Worden at Owens Corning. While European manufacturers of XPS shifted to either HFC-134A or carbon dioxide in 2002, more stringent energy standards and different construction systems in North America make the same sort of conversion more difficult here, says Worden. European XPS is a higher-density product with a lower R-value.

Expanded polystyrene. Expanded polystyrene (EPS) continues to be made with non-ozone-depleting pentane as the expanding agent. Some manufacturers are using a low-pentane formulation that results in lower pentane emissions. (While not an ozone-depleting compound, pentane can generate ground-level smog.) The more distributed production of EPS, compared with XPS, may reduce shipping energy consumption to some extent.

Flame retardants and polystyrene. All foam plastic insulation materials rely on flame retardants to meet fire-resistance standards. EPS and XPS are produced using the brominated flame retardant HBCD (hexabromocyclododecane) at concentrations of 0.5–2.0% by weight. HBCD is not the focus of as much attention as another class of brominated flame retardants (PBDEs), but some evidence indicates that it is more bioaccumulative than PBDEs and just as likely to be toxic to humans (see EBN Vol. 13, No. 6).

Flame retardants and polyisocyanurate. Ironically, until recently flame retardants were not used in most polyiso insulation. With HCFC blowing agents, this thermoset plastic foam was able to achieve the required Class I fire ratings without any added flame retardant. But with the substitution of pentane blowing agents for HCFC-141b, manufacturers now must add flame retardants. Although manufacturers rarely divulge their formulations (and can apparently get around the requirement to list the flame retardant in the MSDS because it is part of one component or the other (the polyol or isocyanate), the most common flame retardant used in polyiso today is believed to be TCPP (tris(chloropropyl) phosphate), a compound that relies on both phosphorous and chlorine as the fire-retarding components. The typical concentration in the foam insulation is 5–14% by weight. While a halogenated compound, TCPP is much less likely to be a persistent bioaccumulative toxin than HBCD, according to the PBT Profiler software from EPA.

Spray polyurethane. While polyiso manufacturers had to eliminate their use of HCFC-141b by January 1, 2003, manufacturers of closed-cell (high-density) spray polyurethane were given an extension for the transition to non-ozone-depleting blowing agents. HCFC-141b for spray polyurethane cannot be sold after December 31, 2004, though polyurethane installers can use inventoried HCFC-based chemicals until July 1, 2005, according to Ken Gayer, the global business manager for foam blowing agents at Honeywell Specialty Materials, which produces the non-ozone-depleting blowing agent HFC-245fa under the tradename Enovate 3000.

Most spray polyurethane companies are converting to Honeywell's HFC-245fa. While significantly more expensive than HCFC-141b, the resultant foam achieves similar energy performance. The ozone depletion potential of HFC-245fa is zero, but the global warming potential is similar to that of HCFC-141b. Hydrocarbon blowing agents are avoided with spray polyurethane because of flammability concerns and difficulties with the vapor pressure, according to Gayer.


Low-density, open-cell polyurethane produced by Icynene is material- efficient and uses water as the blowing agent.
Open-cell polyurethane, including the products made by Icynene, Inc. and Demilec, Inc. as well as the newer soy-based foams, are produced with water as the blowing agent. They do not achieve R-values as high as those of closed-cell polyurethane, but they are more resource-efficient, using just one-fourth to one-third the material used for a comparable volume of closed-cell polyurethane.

Flame retardants and spray polyurethane. Both closed-cell (high-density) and open-cell (low-density) polyurethane insulation contain flame retardants, but these are non-brominated flame retardants. While manufacturers are reluctant to share this information, the best available information indicates that the two flame retardants most commonly used in spray polyurethane are TCPP, which contains chlorine but not bromine, and RDP (resorcinol-bis-diphenylphosphate), which is totally halogen-free.

Use phase and IAQ concerns

Fiberglass and mineral wool. Concerns about mineral and glass fibers possibly being carcinogenic have been widely publicized over the past ten years—especially by competing industries. These concerns resulted in cancer warning labels being required for most products, but more recently these concerns are waning. In October 2001, IARC changed its classification for fiberglass and mineral wool from "possible human carcinogen" to "not a known human carcinogen." This change has allowed mineral wool (slag wool and rock wool) manufacturers to drop the warning labels.

Fiberglass insulation continues to carry the cancer warnings because, in addition to the IARC listing, the National Toxicology Program added glass fibers to its Report on Carcinogens in 1990. According to Angus Crane, the vice president and general council for NAIMA, glass fibers were added to the NTP possible-carcinogen list because of the IARC-reported studies. Now that IARC has dropped the possible-carcinogen listing for glass fibers, the material is likely to be dropped from the NTP list. NAIMA has petitioned NTP to delist glass fibers, but that process typically takes several years. Crane hopes to see the listing removed in late 2005 or early 2006. If and when that happens, the industry will petition the State of California to remove the requirement under Proposition 65 that fiberglass insulation products include a warning about cancer.

Meanwhile, the carcinogenicity of formaldehyde, which could be released in very small quantities from the phenol-formaldehyde binder used in most fiberglass insulation, has recently been upgraded. In June 2004, IARC changed its classification of formaldehyde from a "probable human carcinogen" to a "confirmed human carcinogen." Most of this binder is volatized and dissipated during a baking stage of the manufacturing process, but residual formaldehyde may remain in the product. Johns Manville, one of the five major producers of fiberglass insulation in North America, switched to 100% acrylic binder for its fiberglass insulation product line in 2002 (see EBN Vol. 11, No. 3). The other major fiberglass insulation manufacturers have all had their products certified as low-emitting by Greenguard™.

Mineral wool. For cavity-fill and attic applications, rock wool and slag wool are similar to fiberglass in look and feel, though the density is greater and the sound control better. The fire resistance of mineral wool is also significantly better than that of fiberglass, because of both the higher density and the significantly higher temperatures required for melting. While these fire-resistance properties used to be a major selling point, greater reliance on sprinklers in buildings, rather than passive fire resistance, is resulting in decreased use of mineral wool, according to Crane of NAIMA.

For below-grade applications, one rigid mineral-wool product, Roxul drainboard, offers superb performance, owing to its hydrophobic properties and its excellent drainage characteristics (see EBN Vol. 4, No. 6). This material has never been actively marketed in the U.S., but Roxul products in general are becoming more widely available here.

Cellulose. Cellulose insulation has never been required to carry indoor air quality warnings, and the fiberglass and mineral wool industries remain upset that their products have come under greater scrutiny than cellulose. "Our competitors have not gone through the testing," said Angus Crane of NAIMA. "It is dangerous to assume that an untested material is safe," he told EBN. The editors at EBN continue to take the position that all fiber insulation products (fiberglass, mineral wool, and cellulose) are safe if properly installed, and we would much prefer to see insulation manufacturers focus on the positive benefits of all insulation, rather than potential risks of their competitors' products. The health concerns with cellulose range from inhalation of dust during installation to VOC emissions from printing inks (which are now almost entirely vegetable-based) and limited evidence of toxicity of boric acid flame retardants. For more on health issues with cellulose insulation see EBN Vol. 2, No. 5.

As for installation and performance, cellulose insulation has evolved considerably over the past 20 years. According to Daniel Lea of CIMA, the average installed density of cellulose insulation has dropped from 2.6 pounds per cubic foot (42 kg/m 3) in 1984 to 1.6 pcf (26 kg/m 3) today. "R for R, today's cellulose insulation products are almost 40% lighter than those of 1984," said Lea. Most cellulose insulation today is being installed as "cellulose wall-cavity spray," a process that has sometimes been referred to as "wet-spray" cellulose. CIMA is trying to discourage the use of the term wet-spray because it implies a process that is far wetter than is the case. "I think there is a perception that the material is applied almost as a fibrous papier-mâché," said Lea. "That is far from the case; if you were to touch wall spray seconds after it's applied, you probably couldn't tell that water was added during the installation process," he said. The typical installed moisture content today is 30–35%, according to Lea, while a moisture content as high as 60% was not uncommon 15 years ago.

Fiber insulation installation. Quality dust masks or respirators should be used while installing fiberglass, mineral wool, and cellulose. (Cotton insulation is the only fiber insulation material that can be installed safely without protective measures.) Building design and detailing should ensure that fibers cannot enter forced-air distribution or ventilation systems. Airtight construction practices should be used to ensure that fiber insulation stays where it was installed.

Polystyrene. Indoor air quality concerns with XPS and EPS are similar to concerns addressed previously relating to manufacturing: the potential release of residual styrene monomer and flame retardants. The brominated flame retardants used in polystyrene present a greater health concern than the nonbrominated flame retardants used in polyisocyanurate, spray polyurethane, and cellulose insulation.

Polyisocyanurate. Now that polyiso is no longer produced with HCFCs, it is the environmentally preferred rigid boardstock insulation for above-grade applications. (Polyiso is not recommended for below-grade applications because it can absorb moisture.) Polyiso manufacturers disagree as to whether rigid foam produced today with hydrocarbon blowing agents achieves an R-value comparable to that of the older material made with HCFC-141b. The conductivity of the hydrocarbon blowing agent is higher than that of HCFC-141b, and this has led Dow Chemical to downgrade the rated R-values for all of its polyiso insulation, including Thermax ®. However, Richard Roe of Atlas Roofing argues that the smaller cell size of foam produced with hydrocarbon blowing agents, the slower diffusion rate of the hydrocarbon out of the polymer cells, and the lower absorption of the hydrocarbon blowing agent by the polymer collectively result in better long-term R-value stability.

Most polyiso manufacturers are now using new long-term thermal resistance (LTTR) values for reporting aged R-values. This method was adopted in Canada in mid-2002 and in the U.S. in January 2003. This method produces 5-year aged R-values that are lower than the 6-month aged R-values that had previously been reported. The bottom line is that the rated long-term stabilized R-value of polyiso is now between R-6 and 6.5 per inch (RSI-42 to 45 per meter), depending on thickness and facings.

Closed-cell polyurethane. Closed-cell, high-density polyurethane is a very good performer owing to the low-conductivity gas in the cellular structure. It is used both for cavity installation and as an insulating roofing material, which is typically referred to as spray polyurethane foam or SPF. The closed-cell structure gives SPF structural properties. There should be no significant impact on R-value with the shift to non-ozone-depleting HFC-245fa blowing agent, which is becoming the industry standard. Polyurethane also exhibits superb adhesive properties and good compressive strength.

Open-cell polyurethane. Open-cell polyurethane is most commonly installed into open cavities, though formulations are available for filling closed cavities from holes at the top. This is a nonstructural foam, though these materials seal very well, and their flexibility allows for some movement of the framing materials as shrinkage and expansion occur. These properties make them very effective insulation materials for older buildings.

Both closed-cell and open-cell polyurethane must be installed by trained professionals. Special care is required to ensure the safety of insulation installers working with these materials; other people should not be in the space while polyurethane insulation is being installed. Once cured, polyurethane insulation is considered by most IAQ experts to be quite inert.

End-of-life reuse and recyclability

Loose-fill and batt insulation. It is difficult to salvage loose-fill or batt insulation and reuse it, though this can be done. Virtually no fiber insulation is recycled after use in buildings—due to contamination with dust and other materials. Scrap insulation generated during installation can be collected and reused quite easily.

Insulation Materials – Summary of Environmental and Health Considerations

[enlarge image]

Rigid boardstock insulation. Rigid insulation can be salvaged and reused if it is protected during removal. For roof insulation applications, reuse is most feasible when protected-membrane or inverted roof configurations are used (see EBN Vol. 7, No. 10). In this system, a non-water-absorbing rigid insulation, such as XPS, is laid on top of the roof membrane, and ballast is installed on top of the insulation. When re-roofing is required, the insulation can be removed and stored for safekeeping, then reinstalled after the new roof membrane is laid down.
Of the rigid insulation materials, only polystyrene can be recycled. This thermoplastic can be melted and re-expanded into either polystyrene insulation or packaging. Unfortunately, very little polystyrene is being recycled currently. Polyiso and polyurethane cannot be recycled because these foams are thermoset plastics.

Final Thoughts and Recommendations

Insulation is a key component of any green building. More important than the decision of what type of insulation to install is the decision of how much insulation should be installed. From an environmental standpoint, a thicker layer of a relatively nongreen insulation material is almost always better than an inadequate thickness of the greenest insulation material available. This point cannot be over-emphasized.

However, assuming that adequate R-values can be achieved, choosing a green insulation material over a nongreen one can be a very good decision. The accompanying table should help to identify materials that meet your needs and satisfy the environmental priorities of your project.

Summary recommendations:

• Provide the highest feasible insulation levels.
• With lower R-value materials, increase insulation thickness.
• Avoid extruded polystyrene due to the ozone-depletion potential of blowing agent.
• Except where moisture may be an issue, use polyiso instead of either XPS or EPS.
• Rigid mineral wool, such as that made by Roxul, is a very good foundation insulation material due to its superb drainage properties.
• With highly conductive framing systems, especially steel, minimize thermal bridging by wrapping the frame with a layer of rigid board insulation.
• Choose high-recycled-content insulation materials when doing so will not result in significant loss of R-value compared with other materials.
• With roof insulation, consider a protected-membrane roof so that insulation can be reused.
• Address air leakage and moisture resistance in insulation detailing. A good source of information on building science issues is http://www.buildingscience.com/.
• For chemically sensitive individuals, test potential insulation materials for reaction before installation.
• Choose an insulation contractor who recycles scrap insulation.

Connect with Scotts Contracting

FB FB Twitter LinkedIn Blog Blog Blog Blog Pinterest